Schneider Circuit Breaker Compact NSX250F TMD 200A 3Pole 3d

Schneider Circuit Breaker Compact NSX250F TMD 200A 3Pole 3d price in Paksitan
Schneider Circuit Breaker Compact NSX250F TMD 200A 3Pole 3d
  • Stock Availability: In Stock
  • Model: SCHR-297
Product Views: 4957
Rs. 82,500/-

OVERVIEW:

Explore w11stop.com, Get latest Schneider & other electronic components at discounted price in Pakistan with free cash on delivery service across Pakistan. We provide Schneider products at official prices from distributor and dealers in Pakistan.

Document:

Product Details
Product Name Schneider Circuit Breaker Compact NSX250F - TMD - 200 A - 3 Pole - 3d
Price Rs. 40,940/-
Capacitance
Breaking capacity 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 600 V AC 50/60 Hz conforming to UL 508 35 kA at 480 V AC 50/60 Hz conforming to UL 508 85 kA at 240 V AC 50/60 Hz conforming to UL 508
Current AC
[In] rated current 250 A ( 40 °C )
Summary
Ambient Air Temperature for Operation -35...70 °C
Ambient Air Temperature for Storage -55...85 °C
Height 161 mm
Range Compact
HARDWARE FEATURES
Auxiliary Contact Composition Without
Depth 86 mm
IK Degree of Protection IK07 conforming to IEC 62262
IP degree of protection IP40 conforming to IEC 60529
Mounting Mode Fixed
Mounting Support Backplate
Network Type AC
Protection Type Overload protection (thermal) L Short-circuit protection (magnetic) I
Trip Unit Rating 200 A ( 40 °C )
Weight 2.4 kg
Type
product or component type Circuit breaker
General Specification
Control Type Toggle
Electrical Durability 10000 cycles 440 V In/2 conforming to IEC 60947-2 15000 cycles 690 V In/2 conforming to IEC 60947-2 20000 cycles 440 V In conforming to IEC 60947-2 7500 cycles 690 V In conforming to IEC 60947-2
Mechanical Durability 40000 cycles
Network Frequency 50/60 Hz
Poles Description 3P
Protected Poles Description 3t
Width 105 mm
[Ics] Rated Service Breaking Capacity Ics 22 kA 525 V AC 50/60 Hz conforming to IEC 60947-2 Ics 30 kA 500 V AC 50/60 Hz conforming to IEC 60947-2 Ics 35 kA 440 V AC 50/60 Hz conforming to IEC 60947-2 Ics 36 kA 380/415 V AC 50/60 Hz conforming to IEC 60947-2 Ics 8 kA 660/690 V AC 50/60 Hz conforming to IEC 60947-2 Ics 85 kA 220/240 V AC 50/60 Hz conforming to IEC 60947-2
[tr] Long-time Delay Adjustment Range 15 s 6 x Ir 120...400 s 1.5 x In
[Ue] Rated Operational Voltage 690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage 8 kV
[Ui] rated insulation voltage 800 V AC 50/60 Hz

Write a review

Note: HTML is not translated!
Bad Good