KYORITSU KEW 5410 RCD Tester

KYORITSU KEW 5410 RCD Tester price in Paksitan
KYORITSU KEW 5410 RCD Tester
  • Stock Availability: In Stock
  • Model: KYOU-01
Product Views: 8809
Rs. 245,000/-

FEATURES:

  • Measurement of RCD trip time Conducting testing of rated residual non-operating currents at × 1/2 Range, measuring RCD trip time at × 1 and × 5 Ranges.
  • Measurement of trip out current Measuring trip out current by varying   current automatically.
  • Remote Test Enabling a user to hold the Test Leads with his both hands by locking the Test Button. Measurement will automatically start when the main voltage is detected.
  • Voltage Measurement Carrying out a constant measurement of voltage in the range
  • stand-by mode at each Range.
  • Auto-detection of Contact voltage detecting the voltage to earth of Earth electrodes or protective conductors during RCD test - when applying test currents - at measurement using EARTH in order to prevent electrical shocks caused by the damaged earth. Measurement will be ceased at AC50V or more.
  • Dust- and Water-proof dust- and Water-proof construction(designed to IEC 60529 IP54).
  • BacklightFacilitating working at dimly illuminated locations.

 

Document:

KYORITSU KEW 5410 RCD Tester

Product Details
Product Name KYORITSU KEW 5410 RCD Tester
Price Rs. 190,000/-
Computers Specs
Rated Voltage 100V±10%, 200V-10%~+32%, 400V±10%, 50/60Hz
Display Specification
Display 1999 counts (3 1/2digits), Large LCD
Summary
Applicable standards IEC 61010-1 Pollution degree2 CAT III 300V / CAT II 400V IEC 61010-031 IEC 61557-1, 6 IEC 60529 (IP54)
Included Accessories 7128A (Test leads) 7129A (Test lead with alligator clip) 8017 (Long pin) × 2 Cord case, 9121 (Shoulder strap), Instruction manual, R6(AA) × 8
Operating temperature & humidity range 0ºC - 40ºC, relative humidity 85% (no condensation)
Optional Accessories 7100A (Precision measurement cord set)
Overload protection Earth Resistance: 280V AC for 10 seconds across 2 of the 3 terminals Earth Voltage: 300V AC for 1 minute
Safety Standard IEC 61010-1 CAT III 300V Pollution Degree 2, IEC 61557
Storage temperature & humidity range -20ºC - 60ºC, relative humidity 85% (no condensation)
Accuracy (Measurement of RCD trip time - Measurement of trip out current) (Trip Time) (× 5) 1%rdg±3dgt, (x 1) 1%rdg±3dgt, (x 1/2) 1%rdg±3dgt, (AUTO RAMP mA) Test Current at each step -4%~+4% (Trip Time) (× 5) +2%~+8%dgt, (x 1) +2%~+8%dgt, (x 1/2) -8%~-2%dgt (Voltage Measurement) 2%rdg±4dgt
Measuring range Testing time = 0ms~200ms Testing time = 0ms~2000ms Testing time = 0ms~2000ms 40% - 110% of lΔn (goes up by 5%) Testing time 300ms × 15steps (Voltage Measurement) 80V~450V 50/60Hz
Weight Approx. 965g (including batteries)
Insulation Resistance 50MΩ or more / 1000V (between electrical circuit and enclosure)
Range (x 5) (x 1) (x 1/2) (AUTO RAMP mA)
Test Current (approx.) 15/30/50/100mA, 15/30/50/100/200/500mA, 15/30/50/100/200/500mA
Power Source DC 12V / R6(AA)(1.5V) × 8
General Specification
Dimensions 167(L)×186(W)×89(D)mm

Write a review

Note: HTML is not translated!
Bad Good